Monitoring and Signalling Devices

SIGNALING DEVICES

Automated processes use intelligent signaling systems to keep you informed at all times about the status of your entire plant and any faults that may arise. You can even install signaling devices for rupture discs that have already been installed.

NIMU

NIMU (Non-Invasive Monitoring Unit) is a reusable monitoring system, which informs the operator as soon as the rupture disc responds to an overpressure or vacuum situation.

The unit is installed in a blind tapping in the outlet section of the rupture disc holder. This completely isolates NIMU from the process and prevents potential leakages.

After a rupture disc has opened, only the rupture disc itself must be replaced. This reduces production downtime and associated costs to a minimum. NIMU is based on tried and tested, intrinsically safe, closed circuit technology and is therefore easy to integrate into process control systems.

Rupture disc / bursting disc with signaling device NIMU
NIMU signaling device

SNR

This signaling unit was specifically developed for bi-directional rupture discs. The SNR uses a proximity switch, which offers inductive, intrinsically safe monitoring in accordance with NAMUR (EN 60947-5-6) for compliance with the highest safety standards.

signaling device SNR for rupture discs / bursting discs
SNR signaling device

SK

The SK signaling unit uses the closed-circuit current principle. A signaling cable is integrated into the rupture disc during the manufacturing process to create a highly reliable unit. When the rupture disc opens, the signaling cable circuit is broken and a corresponding signal sent to the process control system.

SR: As an installation aid, the SK signaling device can be supplemented with an additional spacer ring and cable gland.

signaling device SK for rupture discs / bursting discs
SK signaling device

BIRD

The BIRD signaling device contains a ceramic bar with integrated electrical conductors which are broken when the rupture disc opens. The standard version of BIRD is temperature-resistant up to 302 °F, the high temperature version is capable of operating at temperatures of up
to 752 °F.

signaling device BIRD for rupture discs / bursting discs
BIRD signaling device

SLL

The SLL sensor transmits infra-red beams using optical fibres. These hit the reflector on a rupture disc and are registered by the SLL receiver. Both the transmitter and receiver are integrated in the SLL sensor head. When the rupture disc opens, the reflection is broken and a signal is transmitted from the SLL receiver to the connected process control system.

Rupture disc / bursting disc with signaling device SLL
SLL signaling device

SB/SB-S

Like the SK signaling device, this signaling system uses the principle of closed circuit technology. The signaling membrane is mounted directly between the flanges on the venting side of the rupture disc. When the rupture disc breaks, the pressure of the discharging process medium destroys the SB-S membrane and the intrinsically safe circuit is broken. This sends an error message to the process control system. Also available without a relief bore for monitoring leakages.

Signal Rupture disc / bursting disc SB/SB-S
SB/SB-S signaling device

FOS

The fibre optic FOS rupture membrane is used to monitor leakages and the response of rupture discs under highly corrosive conditions and in hazardous areas where electrical connections are not possible.

The signaling element carries no current and consists of a glass fibre with a thickness of < 250 μm. When the rupture disc opens, the optical fibre circuit tears and the circuit is broken.

The downstream evaluation unit transmits a signal, which can be used to trigger visual or acoustic alarms and to shut down the plant.

Signal Rupture disc / bursting disc FOS
FOS signaling device

Description

Monitoring and Signalling Devices Downloads

Process Safety Brochure